PM8ECCMIB DEFINITIONS ::= BEGIN
    IMPORTS
    enterprises
        FROM RFC1155-SMI
    OBJECT-TYPE
        FROM RFC-1212
    TRAP-TYPE
        FROM RFC-1215;

    AlarmType ::= INTEGER {
                                overValue( 10 ),
                                overPower( 11 ),
                                overReversePower( 12 ),
                                underValue( 20 ),
                                underPower( 21 ),
                                phaseRotationReversal( 51 ),
                                phaseLossVoltage( 52 ),
                                phaseLossCurrent( 53 ),
                                powerFactorLeading( 54 ),
                                powerFactorLagging( 55 ),
                                digitalInputOFFtoON( 60 ),
                                digitalInputONtoOFF( 61 ),
                                unaryEvent( 70 ),
                                voltageOrCurrentSwell( 80 ),
                                voltageOrCurrentSag( 90 ),
                                combinatorialAND( 100 ),
                                combinatorialNAND( 101 ),
                                combinatorialOR( 102 ),
                                combinatorialNOR( 103 ),
                                combinatorialXOR( 104 ),
                                combinatorialNOT( 105 ),
                                diagnostic( 1280 )
                            }

    IOPointType ::= INTEGER {
                                digitalInput( 1 ),
                                digitalOutput( 2 ),
                                analogInput( 3 ),
                                analogOutput( 4 )
                            }

    IOPointLabel ::= OCTET STRING (SIZE(0..16))

    AlarmLabel ::= OCTET STRING (SIZE(0..16))



    schneiderElectric OBJECT IDENTIFIER ::= { enterprises 3833 }

    transparentFactoryEthernet OBJECT IDENTIFIER ::= { schneiderElectric 1 }

    equipmentProfile OBJECT IDENTIFIER ::= { transparentFactoryEthernet 7 }

    tfProducts OBJECT IDENTIFIER ::= { equipmentProfile 255 }

    ecc OBJECT IDENTIFIER ::= { tfProducts 15 }

    pm8ecc OBJECT IDENTIFIER ::= { ecc 1 }

    metering OBJECT IDENTIFIER ::= { pm8ecc 1 }

    systemWiringTypeTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF SystemWiringTypeEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "The wiring system type of the host meter."
        ::= { metering 1 }

    systemWiringTypeEntry OBJECT-TYPE
        SYNTAX              SystemWiringTypeEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter System Wiring Type"
        INDEX               {
                                swtIndex
                            }
        ::= { systemWiringTypeTable 1 }

    SystemWiringTypeEntry ::= SEQUENCE {
        swtIndex
            INTEGER,
        swtWiringType
            INTEGER
    }

    swtIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "System Wiring Type Table Index"
        ::= { systemWiringTypeEntry 1 }

    swtWiringType OBJECT-TYPE
        SYNTAX              INTEGER (10 | 11 | 12 | 30 | 31 | 32 | 40 | 42 | 44)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Single Phase Line to Neutral 2 Wire 1CT 1PT is
                            '10' Single Phase Line to Line 2 Wire 1CT 1PT
                            is '11' Single Phase 3-Wire 3 wire 2CT 2PT is
                            '12' Three Phase 3 Wire 2CT 2PT is '30' Three
                            Phase 3 Wire 3CT 2PT is '31' Three Phase 3 Wire
                            1CT 2PT is '32' Three Phase 4 Wire 3CT 3PT is
                            '40' Three Phase 4 Wire 3CT 2PT is '42' Three
                            Phase 4 Wire 1CT 3PT is '44'"
        ::= { systemWiringTypeEntry 2 }

    loadCurrentTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF LoadCurrentEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Load Current Table"
        ::= { metering 2 }

    loadCurrentEntry OBJECT-TYPE
        SYNTAX              LoadCurrentEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Load Current Table"
        INDEX               {
                                lcIndex
                            }
        ::= { loadCurrentTable 1 }

    LoadCurrentEntry ::= SEQUENCE {
        lcIndex
            INTEGER,
        lcIa
            OCTET STRING,
        lcIb
            OCTET STRING,
        lcIc
            OCTET STRING,
        lcIAvg
            OCTET STRING
    }

    lcIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Load Current Table Index"
        ::= { loadCurrentEntry 1 }

    lcIa OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Load Current Phase A Units = A (Amps)"
        ::= { loadCurrentEntry 2 }

    lcIb OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Load Current Phase B Units = A (Amps)"
        ::= { loadCurrentEntry 3 }

    lcIc OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Load Current Phase C Units = A (Amps)"
        ::= { loadCurrentEntry 4 }

    lcIAvg OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Load Current 3 Phase Average Units
                            = A (Amps)"
        ::= { loadCurrentEntry 5 }

    powerTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF PowerEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Table"
        ::= { metering 3 }

    powerEntry OBJECT-TYPE
        SYNTAX              PowerEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Table"
        INDEX               {
                                pIndex
                            }
        ::= { powerTable 1 }

    PowerEntry ::= SEQUENCE {
        pIndex
            INTEGER,
        pReal
            OCTET STRING,
        pReactive
            OCTET STRING,
        pApparent
            OCTET STRING
    }

    pIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Power Table Index"
        ::= { powerEntry 1 }

    pReal OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Real Power Units = kW"
        ::= { powerEntry 2 }

    pReactive OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Reactive Power Units = kVAR"
        ::= { powerEntry 3 }

    pApparent OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Apparent Power Units = kVA"
        ::= { powerEntry 4 }

    powerFactorTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF PowerFactorEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Factor Table"
        ::= { metering 4 }

    powerFactorEntry OBJECT-TYPE
        SYNTAX              PowerFactorEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Factor Table"
        INDEX               {
                                pfIndex
                            }
        ::= { powerFactorTable 1 }

    PowerFactorEntry ::= SEQUENCE {
        pfIndex
            INTEGER,
        pfPowerFactorTotal
            OCTET STRING,
        pfPowerFactorDescription
            OCTET STRING
    }

    pfIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Power Factor Table Index"
        ::= { powerFactorEntry 1 }

    pfPowerFactorTotal OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter 3 Phase Total Power Factor"
        ::= { powerFactorEntry 2 }

    pfPowerFactorDescription OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Describes the current power factor Lead/Lag for
                            IEEE mode Cap/Ind for IEC mode"
        ::= { powerFactorEntry 3 }

    voltageTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF VoltageEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Table"
        ::= { metering 5 }

    voltageEntry OBJECT-TYPE
        SYNTAX              VoltageEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Table"
        INDEX               {
                                vIndex
                            }
        ::= { voltageTable 1 }

    VoltageEntry ::= SEQUENCE {
        vIndex
            INTEGER,
        vVab
            OCTET STRING,
        vVbc
            OCTET STRING,
        vVca
            OCTET STRING,
        vVllAvg
            OCTET STRING,
        vVan
            OCTET STRING,
        vVbn
            OCTET STRING,
        vVcn
            OCTET STRING,
        vVlnAvg
            OCTET STRING
    }

    vIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Voltage Table Index"
        ::= { voltageEntry 1 }

    vVab OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line A to Line B Units = V
                            (Volts)"
        ::= { voltageEntry 2 }

    vVbc OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line B to Line C Units = V
                            (Volts)"
        ::= { voltageEntry 3 }

    vVca OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line C to Line A Units = V
                            (Volts)"
        ::= { voltageEntry 4 }

    vVllAvg OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line to Line Average Voltage
                            Units = V (Volts)"
        ::= { voltageEntry 5 }

    vVan OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line A to Neutral Units = V
                            (Volts)"
        ::= { voltageEntry 6 }

    vVbn OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line B to Neutral Units = V
                            (Volts)"
        ::= { voltageEntry 7 }

    vVcn OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line C to Neutral Units = V
                            (Volts)"
        ::= { voltageEntry 8 }

    vVlnAvg OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Voltage Line to Neutral 3 Phase Average
                            Units = V (Volts)"
        ::= { voltageEntry 9 }

    frequencyTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF FrequencyEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Frequency Table"
        ::= { metering 6 }

    frequencyEntry OBJECT-TYPE
        SYNTAX              FrequencyEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Frequency Table"
        INDEX               {
                                fIndex
                            }
        ::= { frequencyTable 1 }

    FrequencyEntry ::= SEQUENCE {
        fIndex
            INTEGER,
        fFrequency
            OCTET STRING
    }

    fIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Frequency Table Index"
        ::= { frequencyEntry 1 }

    fFrequency OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Frequency Units = Hz"
        ::= { frequencyEntry 2 }

    currentDemandTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF CurrentDemandEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Current Demand Table"
        ::= { metering 7 }

    currentDemandEntry OBJECT-TYPE
        SYNTAX              CurrentDemandEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Current Demand Table"
        INDEX               {
                                cdPhase,
                                cdIndex
                            }
        ::= { currentDemandTable 1 }

    CurrentDemandEntry ::= SEQUENCE {
        cdIndex
            INTEGER,
        cdPhase
            OCTET STRING,
        cdPresentCurrentDemand
            OCTET STRING,
        cdPeakCurrentDemand
            OCTET STRING,
        cdLastCurrentDemand
            OCTET STRING,
        cdPeakDateTime
            OCTET STRING,
        cdResetDateTime
            OCTET STRING,
        cdPhaseEnum
            INTEGER
    }

    cdIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Demand Current Table Index"
        ::= { currentDemandEntry 1 }

    cdPhase OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(2))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Current Demand Phase Name"
        ::= { currentDemandEntry 2 }

    cdPresentCurrentDemand OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Present Demand Current Units = A (Amps)"
        ::= { currentDemandEntry 3 }

    cdPeakCurrentDemand OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Peak Current Demand Units = A (Amps)"
        ::= { currentDemandEntry 4 }

    cdLastCurrentDemand OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Current Demand Last Interval Units
                            = A (Amps)"
        ::= { currentDemandEntry 5 }

    cdPeakDateTime OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Peak Current Demand Date and Time"
        ::= { currentDemandEntry 6 }

    cdResetDateTime OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Date and Time of Demand Current Reset"
        ::= { currentDemandEntry 7 }

    cdPhaseEnum OBJECT-TYPE
        SYNTAX              INTEGER {
                                currentPhaseA( 1 ),
                                currentPhaseB( 2 ),
                                currentPhaseC( 3 )
                            }
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Current Demand Phase"
        ::= { currentDemandEntry 8 }

    powerDemandTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF PowerDemandEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Demand"
        ::= { metering 8 }

    powerDemandEntry OBJECT-TYPE
        SYNTAX              PowerDemandEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Demand Table"
        INDEX               {
                                pdComponent,
                                pdIndex
                            }
        ::= { powerDemandTable 1 }

    PowerDemandEntry ::= SEQUENCE {
        pdIndex
            INTEGER,
        pdComponent
            OCTET STRING,
        pdPresentPowerDemand
            OCTET STRING,
        pdPeakPowerDemand
            OCTET STRING,
        pdLastPowerDemand
            OCTET STRING,
        pdPeakDateTime
            OCTET STRING,
        pdResetDateTime
            OCTET STRING,
        pdComponentEnum
            INTEGER
    }

    pdIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Power Demand Table Index"
        ::= { powerDemandEntry 1 }

    pdComponent OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(4..8))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Demand Component Units: Real
                            = kW Reacitve = kVAR Apparent = kVA"
        ::= { powerDemandEntry 2 }

    pdPresentPowerDemand OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Present Demand Power"
        ::= { powerDemandEntry 3 }

    pdPeakPowerDemand OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Peak Power Demand"
        ::= { powerDemandEntry 4 }

    pdLastPowerDemand OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Demand Last Interval"
        ::= { powerDemandEntry 5 }

    pdPeakDateTime OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Peak Power Demand Date and Time"
        ::= { powerDemandEntry 6 }

    pdResetDateTime OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Date and Time of Power Demand Reset"
        ::= { powerDemandEntry 7 }

    pdComponentEnum OBJECT-TYPE
        SYNTAX              INTEGER {
                                realPower( 1 ),
                                reactivePower( 2 ),
                                apparentPower( 3 )
                            }
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Power Demand Component"
        ::= { powerDemandEntry 8 }

    energyTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF EnergyEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Energy Table"
        ::= { metering 9 }

    energyEntry OBJECT-TYPE
        SYNTAX              EnergyEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Energy Table"
        INDEX               {
                                eIndex
                            }
        ::= { energyTable 1 }

    EnergyEntry ::= SEQUENCE {
        eIndex
            INTEGER,
        eRealEnergy
            OCTET STRING,
        eDateTimeRealEnergyReset
            OCTET STRING,
        eReactiveEnergy
            OCTET STRING,
        eDateTimeReactiveEnergyReset
            OCTET STRING,
        eApparentEnergy
            OCTET STRING,
        eDateTimeApparentEnergyReset
            OCTET STRING
    }

    eIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Energy Table Index"
        ::= { energyEntry 1 }

    eRealEnergy OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Real Energy Units = kWh"
        ::= { energyEntry 2 }

    eDateTimeRealEnergyReset OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Date and Time Real Energy Accumulation
                            was reset"
        ::= { energyEntry 3 }

    eReactiveEnergy OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Reactive Energy Units = kVARh"
        ::= { energyEntry 4 }

    eDateTimeReactiveEnergyReset OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Date and Time Reative Energy Accumulation
                            was reset"
        ::= { energyEntry 5 }

    eApparentEnergy OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Apparent Energy Units = kVAh"
        ::= { energyEntry 6 }

    eDateTimeApparentEnergyReset OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Date and Time Reactive Energy Accumulation
                            was reset"
        ::= { energyEntry 7 }

    alarms OBJECT IDENTIFIER ::= { pm8ecc 2 }

    alarmConfigurationTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF AlarmConfigurationEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Displays the current configuration of the Host
                            Meter On-board alarms"
        ::= { alarms 1 }

    alarmConfigurationEntry OBJECT-TYPE
        SYNTAX              AlarmConfigurationEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Contains configuration information for the Host
                            Meter On-board Alarms"
        INDEX               {
                                acIndex,
                                acPosition
                            }
        ::= { alarmConfigurationTable 1 }

    AlarmConfigurationEntry ::= SEQUENCE {
        acIndex
            INTEGER,
        acPosition
            INTEGER,
        acAlarmLabel
            AlarmLabel,
        acEnabled
            INTEGER,
        acStatus
            INTEGER,
        acCounter
            INTEGER,
        acPriority
            INTEGER,
        acType
            AlarmType,
        acAlarmList1
            INTEGER,
        acAlarmList2
            INTEGER,
        acAlarmList3
            INTEGER,
        acAlarmList4
            INTEGER
    }

    acIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Alarm Configuration Table Index"
        ::= { alarmConfigurationEntry 1 }

    acPosition OBJECT-TYPE
        SYNTAX              INTEGER (1..74)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the position of the alarm. 1 - 74"
        ::= { alarmConfigurationEntry 2 }

    acAlarmLabel OBJECT-TYPE
        SYNTAX              AlarmLabel
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The name of the alarm (user configurable)"
        ::= { alarmConfigurationEntry 3 }

    acEnabled OBJECT-TYPE
        SYNTAX              INTEGER (0 | 255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates whether the alarm is enabled or not.
                            0 = Disabled 255 = Enabled"
        ::= { alarmConfigurationEntry 4 }

    acStatus OBJECT-TYPE
        SYNTAX              INTEGER (0..1)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates whether the alarm is active. 0 = Inactive
                            1 = Active"
        ::= { alarmConfigurationEntry 5 }

    acCounter OBJECT-TYPE
        SYNTAX              INTEGER (0..32767)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the number of times the alarm has been
                            activated. Note: This counter resets at 32767"
        ::= { alarmConfigurationEntry 6 }

    acPriority OBJECT-TYPE
        SYNTAX              INTEGER (0..3)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The priority of the alarm. 0 = No Priority 1 =
                            Low Priority 2 = Medium Priority 3 = High Priority"
        ::= { alarmConfigurationEntry 7 }

    acType OBJECT-TYPE
        SYNTAX              AlarmType
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the type of the alarm."
        ::= { alarmConfigurationEntry 8 }

    acAlarmList1 OBJECT-TYPE
        SYNTAX              INTEGER
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Used for combinatorial type alarms - The position
                            of the first alarm that is used to evaluate the
                            alarm state."
        ::= { alarmConfigurationEntry 9 }

    acAlarmList2 OBJECT-TYPE
        SYNTAX              INTEGER
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Used for combinatorial type alarms - The position
                            of the second alarm that is used to evaluate
                            the alarm state."
        ::= { alarmConfigurationEntry 10 }

    acAlarmList3 OBJECT-TYPE
        SYNTAX              INTEGER
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Used for combinatorial type alarms - The position
                            of the third alarm that is used to evaluate the
                            alarm state."
        ::= { alarmConfigurationEntry 11 }

    acAlarmList4 OBJECT-TYPE
        SYNTAX              INTEGER
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Used for combinatorial type alarms - The position
                            of the fourth alarm that is used to evaluate
                            the alarm state."
        ::= { alarmConfigurationEntry 12 }

    alarmSummaryBitmapsTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF AlarmSummaryBitmapsEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Indicates the state of the Host Meter On-Board
                            Alarms"
        ::= { alarms 2 }

    alarmSummaryBitmapsEntry OBJECT-TYPE
        SYNTAX              AlarmSummaryBitmapsEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Indicates the status of the Host Meter On-Board
                            Alarms"
        INDEX               {
                                alSumIndex
                            }
        ::= { alarmSummaryBitmapsTable 1 }

    AlarmSummaryBitmapsEntry ::= SEQUENCE {
        alSumIndex
            INTEGER,
        alSumAlarms1to16
            OCTET STRING,
        alSumAlarms17to32
            OCTET STRING,
        alSumAlarms33to48
            OCTET STRING,
        alSumAlarms49to64
            OCTET STRING,
        alSumAlarms65to74
            OCTET STRING
    }

    alSumIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Alarm Summary Bitmap Table Index"
        ::= { alarmSummaryBitmapsEntry 1 }

    alSumAlarms1to16 OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(16))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the status of Alarms 1 - 16 (16-bits,
                            bit-0 = Alarm 1)"
        ::= { alarmSummaryBitmapsEntry 2 }

    alSumAlarms17to32 OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(16))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the status of Alarms 17 - 32 (16-bits,
                            bit-0 = Alarm 17)"
        ::= { alarmSummaryBitmapsEntry 3 }

    alSumAlarms33to48 OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(16))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the status of Alarms 33 - 48 (16-bits,
                            bit-0 = Alarm 33)"
        ::= { alarmSummaryBitmapsEntry 4 }

    alSumAlarms49to64 OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(16))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the status of Alarms 49 - 64 (16-bits,
                            bit-0 = Alarm 49)"
        ::= { alarmSummaryBitmapsEntry 5 }

    alSumAlarms65to74 OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(16))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the status of Alarms 65 - 74 (16-bits,
                            bit-0 = Alarm 65, bit-9 = Alarm 74)"
        ::= { alarmSummaryBitmapsEntry 6 }

    alarmCountersTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF AlarmCountersEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter On-Board Alarm Counters"
        ::= { alarms 3 }

    alarmCountersEntry OBJECT-TYPE
        SYNTAX              AlarmCountersEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter On-Board Alarm Counters"
        INDEX               {
                                alCntAlarmPosition,
                                alCntIndex
                            }
        ::= { alarmCountersTable 1 }

    AlarmCountersEntry ::= SEQUENCE {
        alCntIndex
            INTEGER,
        alCntAlarmPosition
            INTEGER,
        alCntCount
            INTEGER
    }

    alCntIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Alarm Counters Table Index"
        ::= { alarmCountersEntry 1 }

    alCntAlarmPosition OBJECT-TYPE
        SYNTAX              INTEGER (1..74)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The Host Meter Alarm Position"
        ::= { alarmCountersEntry 2 }

    alCntCount OBJECT-TYPE
        SYNTAX              INTEGER (0..65535)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The number of times the Host Meter On-Board alarm
                            has transitioned from an inactive state to an
                            active state"
        ::= { alarmCountersEntry 3 }

    io OBJECT IDENTIFIER ::= { pm8ecc 3 }

    ioOptionIDTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF IoOptionIDEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "I/O Option Module Installed on the Host Meter"
        ::= { io 1 }

    ioOptionIDEntry OBJECT-TYPE
        SYNTAX              IoOptionIDEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "I/O Option Card Installed On-board the Host Meter"
        INDEX               {
                                ioIDIndex
                            }
        ::= { ioOptionIDTable 1 }

    IoOptionIDEntry ::= SEQUENCE {
        ioIDIndex
            INTEGER,
        ioIDInstalledOptionSlot1
            INTEGER,
        ioIDInstalledOptionSlot2
            INTEGER
    }

    ioIDIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "I/O Installed Option ID Table Index"
        ::= { ioOptionIDEntry 1 }

    ioIDInstalledOptionSlot1 OBJECT-TYPE
        SYNTAX              INTEGER {
                                unused( 1 ),
                                io-22( 2 ),
                                io-26( 3 ),
                                io-2222( 4 )
                            }
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
                            4 = IO 2222"
        ::= { ioOptionIDEntry 2 }

    ioIDInstalledOptionSlot2 OBJECT-TYPE
        SYNTAX              INTEGER {
                                unused( 1 ),
                                io-22( 2 ),
                                io-26( 3 ),
                                io-2222( 4 )
                            }
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
                            4 = IO 2222"
        ::= { ioOptionIDEntry 3 }

    ioConfigurationTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF IoConfigurationEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Displays the current I/O configuration for each
                            I/O point"
        ::= { io 2 }

    ioConfigurationEntry OBJECT-TYPE
        SYNTAX              IoConfigurationEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Contains configuration information for the Host
                            Meter On-board I/O"
        INDEX               {
                                iocIndex,
                                iocPointNumber
                            }
        ::= { ioConfigurationTable 1 }

    IoConfigurationEntry ::= SEQUENCE {
        iocIndex
            INTEGER,
        iocPointNumber
            INTEGER,
        iocLabel
            IOPointLabel,
        iocStateOrValue
            OCTET STRING,
        iocPointType
            IOPointType,
        iocMode
            INTEGER,
        iocType
            INTEGER,
        iocCount
            OCTET STRING
    }

    iocIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "I/O Configuration Table Index"
        ::= { ioConfigurationEntry 1 }

    iocPointNumber OBJECT-TYPE
        SYNTAX              INTEGER (1..18)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The point number for this I/O Point"
        ::= { ioConfigurationEntry 2 }

    iocLabel OBJECT-TYPE
        SYNTAX              IOPointLabel
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The name of the I/O Point (user configurable)"
        ::= { ioConfigurationEntry 3 }

    iocStateOrValue OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Displays the current value for the I/O Point Digial
                            I/O: 1 = Active or 0 = Inactive
                            
                            Analog I/O: Scaled input/output value"
        ::= { ioConfigurationEntry 4 }

    iocPointType OBJECT-TYPE
        SYNTAX              IOPointType
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The type of I/O at this point"
        ::= { ioConfigurationEntry 5 }

    iocMode OBJECT-TYPE
        SYNTAX              INTEGER (0..9)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "For Digital Inputs and Outputs this object is
                            always 0 indicating “Discrete”.
                            
                            For Analog Inputs and Outputs this object indicates
                            the range of analog I/O values (used without
                            units) 0 = 0 – 1 1 = 0 – 5 2 = 0 – 10 3 = 0 –
                            20 4 = 1 – 5 5 = 4 – 20 6 = -5 – 5 7 = -10 –
                            10 8 = -100 – 100 9 = User defined (values default
                            to 0)"
        ::= { ioConfigurationEntry 6 }

    iocType OBJECT-TYPE
        SYNTAX              INTEGER
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "For Digital Inputs this object indicates input
                            type 1 = Unused 2 = AC/DC
                            
                            For Digital Outputs this object indicates output
                            type 1 = solid state relay 2 = electromechanical
                            relay
                            
                            For Analog Inputs and Outputs this object indicates
                            the digital resolution of the I/O hardware. 0
                            = 8-Bit, unipolar 1 = 10-Bit, unipolar 2 = 12-Bit,
                            unipolar 3 = 14-Bit, unipolar 4 = 16-Bit, unipolar
                            5 = 16-Bit, bipolar with sign 6 = reserved 7
                            = reserved 8 = Resolution for IO2222 Voltage
                            range 0 - 4000 9 = Resolution for IO2222 Current
                            range 800 - 4000"
        ::= { ioConfigurationEntry 7 }

    iocCount OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(8))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Number of times digital I/O point has transitioned
                            from OFF to ON"
        ::= { ioConfigurationEntry 8 }

    ioStatusBitmapsTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF IoStatusBitmapsEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter I/O Status Bitmaps"
        ::= { io 3 }

    ioStatusBitmapsEntry OBJECT-TYPE
        SYNTAX              IoStatusBitmapsEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter On-Board I/O Status Bitmaps"
        INDEX               {
                                ioStatIndex
                            }
        ::= { ioStatusBitmapsTable 1 }

    IoStatusBitmapsEntry ::= SEQUENCE {
        ioStatIndex
            INTEGER,
        ioStatSummaryBitmap
            OCTET STRING
    }

    ioStatIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "I/O Summary Bitmaps Table Index"
        ::= { ioStatusBitmapsEntry 1 }

    ioStatSummaryBitmap OBJECT-TYPE
        SYNTAX              OCTET STRING (SIZE(18))
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Indicates the Status of the Host Meter I/O Points
                            Bit-0 = I/O Point 1 Bit-1 = I/O Point 2 ... Bit-17
                            = I/O Point 18"
        ::= { ioStatusBitmapsEntry 2 }

    meterSystem OBJECT IDENTIFIER ::= { pm8ecc 4 }

    meterIdentificationTable OBJECT-TYPE
        SYNTAX              SEQUENCE OF MeterIdentificationEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Identification"
        ::= { meterSystem 1 }

    meterIdentificationEntry OBJECT-TYPE
        SYNTAX              MeterIdentificationEntry
        ACCESS              not-accessible
        STATUS              mandatory
        DESCRIPTION         "Host Meter Identification"
        INDEX               {
                                midIndex
                            }
        ::= { meterIdentificationTable 1 }

    MeterIdentificationEntry ::= SEQUENCE {
        midIndex
            INTEGER,
        midSerialNumber
            INTEGER,
        midFirmwareVersion
            OCTET STRING,
        midModelNumber
            OCTET STRING,
        midDeviceName
            OCTET STRING
    }

    midIndex OBJECT-TYPE
        SYNTAX              INTEGER (1..255)
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Meter Identification Table Index"
        ::= { meterIdentificationEntry 1 }

    midSerialNumber OBJECT-TYPE
        SYNTAX              INTEGER
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host meter 32 bit Serial Number"
        ::= { meterIdentificationEntry 2 }

    midFirmwareVersion OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Firmware Version"
        ::= { meterIdentificationEntry 3 }

    midModelNumber OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Model Number"
        ::= { meterIdentificationEntry 4 }

    midDeviceName OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "Host Meter Label plus Nameplate"
        ::= { meterIdentificationEntry 5 }

    trapVariables OBJECT IDENTIFIER ::= { pm8ecc 5 }

    alarmDateAndTime OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The Date and Time of the alarm state change."
        ::= { trapVariables 1 }

    alarmLabel OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The Descriptive Label given to the alarm"
        ::= { trapVariables 2 }

    alarmState OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The state of the Alarm - pickup, dropout, unary,
                            diagnostic"
        ::= { trapVariables 3 }

    alarmValue OBJECT-TYPE
        SYNTAX              INTEGER
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The value of the alarm when it changed state."
        ::= { trapVariables 4 }

    alarmPriority OBJECT-TYPE
        SYNTAX              INTEGER {
                                highPriority( 1 ),
                                mediumPriority( 2 ),
                                lowPriority( 3 )
                            }
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "The priority defined for the alarm."
        ::= { trapVariables 5 }

    mibVersion OBJECT-TYPE
        SYNTAX              OCTET STRING
        ACCESS              read-only
        STATUS              mandatory
        DESCRIPTION         "This is the current version of the MIB"
        ::= { pm8ecc 6 }


    pm8OnBoardAlarmP1 TRAP-TYPE
        ENTERPRISE          pm8ecc
        VARIABLES           {
                                alarmDateAndTime,
                                alarmLabel,
                                alarmState,
                                alarmValue,
                                alarmPriority
                            }
        DESCRIPTION         "Indicates the Host Meter On-Board Alarm system has
                             detected a state change of an enabled alarm with a
                             priority of 1"
        ::= 1

    pm8OnBoardAlarmP2 TRAP-TYPE
        ENTERPRISE          pm8ecc
        VARIABLES           {
                                alarmDateAndTime,
                                alarmLabel,
                                alarmState,
                                alarmValue,
                                alarmPriority
                            }
        DESCRIPTION         "Indicates the Host Meter On-Board Alarm system has
                             detected a state change of an enabled alarm with a
                             priority of 2"
        ::= 2

    pm8OnBoardAlarmP3 TRAP-TYPE
        ENTERPRISE          pm8ecc
        VARIABLES           {
                                alarmDateAndTime,
                                alarmLabel,
                                alarmState,
                                alarmValue,
                                alarmPriority
                            }
        DESCRIPTION         "Indicates the Host Meter On-Board Alarm system has
                             detected a state change of an enabled alarm with a
                             priority of 3"
        ::= 3


END